ZW10-12G/630A Outdoor Vacuum Circuit Breaker | 12kV Rural and Urban Distribution Protection Equipment
I. Overview
ZW10-12G/630A Outdoor Vacuum Circuit Breaker is a three-phase AC outdoor high voltage switchgear, mainly used in 12kV class, rated current 630A, rated frequency 50Hz distribution systems for rural networks, urban networks, mines, railways and ports, especially suitable for outdoor overhead lines, making and breaking load current, overcurrent and short-circuit current, for switching and protecting the power grid.
The circuit breaker can be equipped with an isolating switch according to user needs. A voltage transformer can be installed inside the product as an operating power source. The overall structure of the circuit breaker is three-phase common enclosure type, with sealed housing and composite insulation structure inside, featuring anti-condensation and anti-pollution characteristics, with high insulation level.
II. Service Environment Conditions
- Ambient air temperature: upper limit +40degC, lower limit -40degC;
- Altitude: ≤2000m (if altitude increases, rated insulation level shall be increased accordingly);
- Wind pressure: not exceeding 700Pa (equivalent to wind speed 34m/s);
- Seismic intensity: not exceeding 8 degrees;
- Pollution level: Class IV;
- Maximum daily temperature difference: not exceeding 25degC;
- Relative humidity: daily average ≤95%, monthly average ≤90%;
- No flammable, explosive, chemical corrosion or severe vibration at the place of use.
III. Model and Meaning

Circuit Breaker Assembly Adjustment Parameters
| No. |
Item |
Unit |
Parameter |
| 1 |
Rated Voltage |
kV |
12 |
| 2 |
Rated Current |
A |
630 |
| 3 |
Rated Frequency |
Hz |
50 |
| 4 |
Power Frequency Withstand Voltage |
kV |
42/48 |
| 5 |
Lightning Impulse Voltage (Peak) |
kV |
75/85 |
| 6 |
Rated Short-circuit Breaking Current |
kA |
6.3 |
12.5 |
16 |
20 |
| 7 |
Rated Short-circuit Making Current (Peak) |
kA |
15 |
31.5 |
40 |
50 |
| 8 |
Rated Short-time Withstand Current |
kA |
6.3 |
12.5 |
16 |
20 |
| 9 |
Rated Peak Withstand Current |
kA |
15 |
31.5 |
40 |
50 |
| 10 |
Rated Operating Sequence |
- |
Open-0.3s-Close-Open-180s-Close-Open |
| 11 |
Rated Short-circuit Current Breaking Times |
times |
30 |
| 12 |
Mechanical Life |
times |
10000 |
| 13 |
Allowable Cumulative Wear Thickness of Moving Contact |
mm |
3 |
4 |
| 14 |
Rated Operating Voltage (with CT type spring operating mechanism) |
Closing Coil |
V |
DC or AC220V |
| Opening Coil |
| 15 |
Overcurrent Release Coil Rated Operating Current |
A |
5 |
| 16 |
Current Transformer Primary/Secondary Current Ratio |
- |
100/5, 200/5, 300/5, 400/5, 630/5 |
| 17 |
Combined Each Phase Main Circuit Resistance |
μΩ |
≤200 |
| 18 | Weight |
kg |
150 |

VI. Ordering Instructions
- Product name, model, rated current, rated voltage, rated breaking current;
- Rated operating voltage and charging motor rated voltage;
- Current transformer ratio and accuracy class;
- Enclosure material and color;
- If there are other special requirements, negotiate when ordering.