Whether the selection of a compact substation is reasonable and whether the installation is standard directly affect power supply reliability and equipment service life. This article provides a complete operational guide from capacity selection, equipment configuration, foundation construction to operation and maintenance.
I. Capacity Selection Method
Transformer Capacity Calculation
The capacity selection of a compact substation takes the transformer capacity as the core parameter. The calculation steps are as follows:
- Calculate the total calculated load (kW) within the power supply area
- Apply a diversity factor (0.7~0.9, depending on load nature)
- Convert to apparent power: S = P_total / (power factor × transformer load factor)
- Select the standard capacity level: 50, 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500kVA
- Reserve 20%~30% margin for future expansion
Calculation Example
For a residential community with total calculated load of 480kW, power factor 0.9, diversity factor 0.8, and transformer load factor 0.75:
S = 480×0.8 / (0.9×0.75) ≈ 569kVA → Select 630kVA compact substation
II. Transformer Type Selection
| Comparison Item | Oil-immersed Transformer | Dry-type Transformer |
| Cost | Lower | Higher (about 1.3~1.5 times) |
| Overload capacity | Strong | Relatively strong |
| Fire resistance | Requires fire isolation | Excellent, suitable for densely populated areas |
| Noise | ≤55dB | ≤65dB |
| Maintenance requirement | Regular oil sample testing required | Basically maintenance-free |
| Applicable scenarios | Outdoor, industrial parks | Residential areas, commercial buildings, underground |
III. Foundation Construction Requirements
- The foundation platform is poured with concrete, with a level and flat surface
- The foundation should be at least 300mm above the surrounding ground to prevent rainwater backflow
- The foundation size should be larger than the compact substation base, leaving at least 200mm on each side
- Embed cable inlet and outlet steel conduits, with diameters meeting cable bending radius requirements
- The gap between the base and foundation should be sealed with cement mortar
IV. Earthing System
- Buried ring earthing electrodes around the foundation; burial depth not less than 0.8m
- Transformer working earthing and lightning protection earthing can share the same earthing system
- At least 2 earthing conductors should be led from the earthing electrode to the compact substation foundation platform
- Earthing resistance value ≤4Ω; if soil resistivity is high, add resistance-reducing agents or increase the number of electrodes
- The metal enclosure of the compact substation and high/low-voltage cabinets should all be reliably earthed
V. Pre-commissioning Inspection
- Doors open and close flexibly, with intact sealing strips
- Operating mechanisms are flexible, and electrical interlock functions are normal
- Main switchgear opening and closing operations are normal
- Instruments and relay protection operate accurately
- Busbar connections are tight, and insulation supports are intact
- Fuse ratings are correct, and settings match the design
VI. Operation and Maintenance Key Points
Routine Inspection
- Check the enclosure sealing for signs of water ingress
- Observe transformer operating temperature; temperature control devices should be normal
- Check whether high- and low-voltage side instrument indications are normal
- Listen to transformer operating sound (uniform "humming" is normal)
- Check that enclosure ventilation openings are unobstructed
Periodic Maintenance
- Conduct preventive tests on surge arresters before the annual thunderstorm season
- For oil-immersed transformers, perform simplified insulating oil tests every 3 years
- Clean enclosure ventilation openings and heat sinks quarterly
- Check tightness of all connection bolts and earthing conductors every six months
- After multiple opening/closing operations of low-voltage circuit breakers, check contact wear
Post-Severe-Weather Handling
After severe weather such as strong winds, heavy rain, or snow/ice, increase inspection frequency. Check for damage or deformation of the enclosure, water ingress, foundation settlement, etc. If abnormalities are found, address them promptly.